ROZ1-K (AS) VFD, EMC - 0.6/1 (1.2) kV Servo Cable for Variable Frequency Drive
Application of VDF Cable
ROZ1-K (AS) VFD EMC 0.6/1 (1.2) is especially suitable for all use where double-screened cables are required in connection with EMC. The cable is used in a variety of industrial and building installations, as well as in public buildings, power plants, and engine installations. It is suitable for use in any environment where 0.6/1 kV screened, halogen-free, 90° C cable is required. The cable is suitable for burial and can be placed outdoors.
Construction of Variable Frequency Drive cables
Conductor
Electrolytic annealed copper, class 5 (flexible), according to EN 60228 and IEC 60228.
Protective Conductor
The ground conductor is divided into three conductors; the equivalent cross-section is approximately 50% of the section of the phase conductor.
For 4G cables, ground conductor has the same cross-section as the phase conductors.
Insulation
Cross-linked polyethylene type XLPE according to IEC 60502-1, type HF XLPE 90ºC according to IEC 60092-360.
The standard identification of insulated conductors is the following:
3 x +3 G Grey + Brown + Black + Green/Yellow (3 G) (from 6 mm2
onwards)
4 G
Grey + Brown + Black + Green/Yellow (up to 4 mm2) Assembly of cores
For 3x+3G cables, the three phase conductors are cabled helically with the three protective conductors distributed in the interstices.
For 4G cables, the three phase conductors and protection conductor are cabled helically.
Screen:
Aluminium-polyester tape screen helically placed over the insulated conductors. Over the tape there is a tinned copper braid screen. The tape and the braid act as a double screen to cut out all of the electromagnetic interference, with a minimum total section of 10% of the phase conductor, ensuring a total shielding coverage.
Outer sheath:
Polyolefin type ST8 according to IEC 60502-1 and type SHF1 according to IEC 60092-360.
Black colour.
The ripcord allows you to tear the outer sheath without damaging the screen.
Technical data
|
Dimension (mm2) |
Current Value (A) |
Packaging |
Diameter (mm)* |
Weight (kg/km)* |
|
3x2,5+3G0,75 |
36 |
D./Cut |
11,2 |
192 |
|
3x6+3G1,5 |
63 |
D./Cut |
15,0 |
390 |
|
3x10+3G1,5 |
86 |
D./Cut |
15,4 |
500 |
|
3x16+3G2,5 |
100 |
D./Cut |
18,5 |
715 |
|
3x25+3G4 |
127 |
D./Cut |
21,1 |
1060 |
|
3x35+3G6 |
158 |
D./Cut |
24,5 |
1475 |
|
3x50+3G10 |
192 |
D./Cut |
28,0 |
2040 |
|
3x70+3G10 |
246 |
D./Cut |
30,8 |
2560 |
|
3x95+3G16 |
298 |
D./Cut |
34,7 |
3420 |
|
3x120+3G16 |
346 |
D./Cut |
38,6 |
4205 |
|
3x150+3G25 |
399 |
D./Cut |
44,3 |
5425 |
|
3x185+3G35 |
456 |
D./Cut |
48,2 |
6655 |
|
3x240+3G50 |
538 |
D./Cut |
55,3 |
8720 |
|
3x300+3G50 |
621 |
D./Cut |
61,4 |
10.465 |